상세 보기
Removal of malodorous gases emitted from a wastewater pumping stations by biological methods
SCOPUS
0초록
To select a promising technologies for removal of odorous gases emitted from a wastewater pump station, four methods such as activated carbon (A/C) adsorption, chemical absorption (acid and alkali scrubber), and two biofilters (polyurethane (PU) and worm cast) were investigated. The average odor removal efficiencies in the PU biofilter and A/C column was over 98%, but in a worm cast biofilter and chemical absorption were below 60-80%. The removal efficiency of PU biofilter was very stable (about 98-99%) in the range of retention times of 4-36s, and a maximum elimination capacity was 1.6×107 OU·m-3·h-1. Deodorization costs for an activated carbon adsorption and a biofiltration method were investigated. With increasing odor intensity, the operating cost of the A/C column increased linearly, but the operating cost of the biofilteration increased slightly. The capital cost in a biofilter is about two times higher than that in an A/C column, but the operating cost is very lower than that of in A/C column. In conclusion, the biofiltration was evaluated one of the most promising technologies to control odor in a wastewater pump station.
키워드
- 제목
- Removal of malodorous gases emitted from a wastewater pumping stations by biological methods
- 저자
- Ryu, H.W.
- 발행일
- 2004
- 유형
- Article
- 저널명
- 한국미생물·생명공학회지
- 권
- 32
- 호
- 3
- 페이지
- 265 ~ 270
- 발행국가
- 대한민국
- 분량
- 6 페이지
- ISSN
- E 2234-1305
P 1598-642X