상세 보기
비절연 2차권선을 이용한 삼상 변압기형 초전도한류기의 고장전류제한 동작 분석
- 한태희;
- 고석철;
- 임성훈
초록
Three-phase transformer type superconducting fault current limiter(SFCL) using secondary windings with non-isolation, which consisted of three-phase transformer windings wound on three legs of E-I iron core and three superconducting modules(SCMs), were suggested and its fault current limiting operations according to ground-fault types were analyzed. To verify the effective operation of three-phase transformer type SFCL using secondary windings with non-isolation, the unsymmetrical ground and the symmetrical ground faults were applied into three-phase power simulated system with the suggested SFCL. From the analysis on the experiment, three-phase transformer type SFCL using secondary windings with non-isolation showed lower power burden of three SCMs compared to the SFCL using secondary winding with isolation, especially in case of an unsymmetrical ground fault occurrence.
키워드
- 제목
- 비절연 2차권선을 이용한 삼상 변압기형 초전도한류기의 고장전류제한 동작 분석
- 제목 (타언어)
- Analysis on Fault Current Limiting Operations of Three-Phase Transformer Type SFCL Using Secondary Windings with Non-Isolation
- 저자
- 한태희; 고석철; 임성훈
- 발행일
- 2023-10
- 저널명
- 조명.전기설비학회논문지
- 권
- 37
- 호
- 5
- 페이지
- 62 ~ 69