초록

Three-phase transformer type superconducting fault current limiter (SFCL) using two superconducting modules (SCMs) between secondary windings, which consisted of three-phase transformer windings wound on three legs of E-I iron core, one SCM with insulated connection with one secondary winding and another SCM with non-insulated connection between other two secondary windings, were suggested. For the suggested three-phase SFCL using two SCMs, its three-phase ground fault current limiting operations were analyzed through phasor diagram from electrical equivalent circuit. To verify three-phase ground fault current limiting operation of three-phase transformer type SFCL using two SCMs between secondary windings, three-phase ground faults were applied into three-phase power simulated system with the suggested SFCL. Through analysis on the test results, three-phase transformer type SFCL using two SCMs between secondary windings was confirmed to have effective three-phase ground fault current limiting operations through quenches of two SCMs.

키워드

Windings; Circuit faults; Fault currents; Phase transformers; Limiting; Power transformer insulation; Iron; Three-phase ground fault current limiting operations; three-phase transformer type superconducting fault current limiter (SFCL); E-I iron core; insulated connection; non-insulated connection; superconducting modules (SCMs); three-phase ground faults; CURRENT LIMITERS
제목
Analysis on Three-Phase Ground Fault Current Limiting Operations of Three-Phase Transformer Type SFCL Using Two Superconducting Modules
저자
Han, Tae-Hee; Ko, Seok-Cheol; Lim, Sung-Hun
DOI
10.1109/TASC.2022.3181571
발행일
2022-09
유형
Article
저널명
IEEE Transactions on Applied Superconductivity
권
32
호
6