배전계통 전압 민감도를 이용한 분산전원 통합 제어 시스템의 수용용량 산정 방법

A Method for Calculation of Hosting Capacity of Integrated DER Management System by Using Voltage Sensitivity in Distribution System
  • 김진수; 
  • 이형진; 
  • 윤상윤; 
  • 김재철

초록

A distribution system has advantages by accommodating DER(Distributed Energy Resource) that it’s available, but the voltage ranges have to be considered in operation. In this paper, a method for calculating maximum hosting capacity of DERMS(Distributed Energy Resource Management System) by using voltage sensitivities according to each DER output which is interconnected to different locations is proposed. Each voltage sensitivity of DER bus is explained by the theorem of superposition and the simple model that consists of impedances. Through the proposed method, the DER’s output limit considering the hosting capacity can be calculated linearly and it can be calculated without iteration.The verification of DER integration is achieved by simulation using IEEE-33 bus case, MATPOWER 7.0, and frequency regulation test signal from PNNL(Pacific Northwest National Laboratory).

키워드

AGC; DERMS; Hosting Capacity; Superposition; Voltage Sensitivity
제목
배전계통 전압 민감도를 이용한 분산전원 통합 제어 시스템의 수용용량 산정 방법
제목 (타언어)
A Method for Calculation of Hosting Capacity of Integrated DER Management System by Using Voltage Sensitivity in Distribution System
저자
김진수; 이형진; 윤상윤; 김재철
DOI
10.5207/JIEIE.2020.34.3.057
발행일
2020-03
저널명
조명.전기설비학회논문지
권
34
호
3
페이지
57 ~ 65