This paper derives the problems that occur when asynchronous transfer in case of phase, frequency, voltage between the emergency generator and the grid and proposed the countermeasure to solve this problem when the transfer switch replace ATS(Automatic Transfer Switch) with CTTS(Closed Transition Transfer Switch) for the non-interrupting switching. In order to simulate above cases, modelling was used the transient analysis program PSCAD/EMTDC. By using this, the customer installed emergency generator and the grid was implemented. We compared three cases of asynchronous transition based on the basic case and proposed improvement by controlling the governor of emergency generator.