이중퀜치를 이용한 삼상변압기형 한류기의 고장전류제한 동작 분석

Analysis on Fault Current Limiting Operation of Three-Phase Transformer Type SFCL Using Double Quench

초록

In this paper, the fault current limiting operations of three-phase transformer type superconducting fault current limiter (SFCL) using double quench, which consisted of E-I iron core with three legs wound by primary and secondary windings and two superconducting modules (SCMs), were analyzed according to three-phase ground fault types. To verify the effective operation of the three-phase transformer type SFCL using double quench, the test circuit for three-phase ground faults was constructed, and the fault current tests were carried out. Through analysis on the fault current test results, the different fault current limiting characteristics of three-phase transformer type SFCL using double quench from three-phase transformer type SFCL using three SCMs were discussed.

키워드

Fault current limiting operationsThree-phase transformer type superconducting fault current limiter (SFCL)Double quenchThree-phase ground fault types
제목
이중퀜치를 이용한 삼상변압기형 한류기의 고장전류제한 동작 분석
제목 (타언어)
Analysis on Fault Current Limiting Operation of Three-Phase Transformer Type SFCL Using Double Quench