상세 보기
초록
Among the high distribution voltage consumers, high-capacity consumers are often applying the grounding resistance method in order to overcome demerits such as erroneous operation of the ground reply or potential increase in the battery at the accident of the isolated neutral system. In this paper, to prevent damage to CLR and GPT in the delay to block the breakdown in the resistance grounded neutral system, this study aims to provide a proper suggestion for continuous rating capacity of GPT to check the appropriateness of CLR size and reduce GPT burden. Thereupon, this study comparatively analyzes CLR current applied in general GPT and the current gained when CLR demanded in the system is used and analyzes the simulated system through simulation using PSCAD/EMTDC in order to suggest GPT’s proper continuous rating capacity.
키워드
- 제목
- 저항접지 시스템에서 지락사고시 CLR과열 소손방지를 위한 GPT 정격용량의 적정성 연구
- 저자
- 신호전; 김진석; 김재철; 박유환; 조만영
- 발행일
- 2012-04
- 저널명
- 전기학회논문지
- 권
- 61
- 호
- 4
- 페이지
- 503 ~ 508
- 언어
- KOR
- 출판사
- 대한전기학회
- 발행국가
- 대한민국
- 분량
- 6 페이지
- ISSN
- E 2287-4364
P 1975-8359