콘크리트에 매입된 기초접지극의 크기 및 설치방법에 관한 고찰

A Consideration of Volume and Installation Method of Concrete-Embedded Foundation Earthed an Electrode

초록

IEC standards do not require to limit the earthing resistance of the concrete-embedded foundation earthing electrode which is installed to a specific value. However, in Korea the value of 5Ω and below applies to the earthing resistance for a domestic customer whose receiving voltage is 22.9kV. This paper calculates the minimum area and volume of the concrete-embedded foundation earthing electrode in order to obtain a specific value of the earthing resistance when the electrode of the building's lightning protection system and that of its power system are interconnected. It also suggested the most appropriate method of installing the foundation earthing electrode, taking the electric characteristics of concrete into account.

키워드

Lightning Protection System; Concrete-Embedded Foundation Earth Electrode; Foundation Earth Electrode
제목
콘크리트에 매입된 기초접지극의 크기 및 설치방법에 관한 고찰
제목 (타언어)
A Consideration of Volume and Installation Method of Concrete-Embedded Foundation Earthed an Electrode
저자
이주철; 이영철; 김재철
발행일
2013-07
저널명
조명.전기설비학회논문지
권
27
호
7
페이지
82 ~ 88