Analysis on current limiting characteristics of a transformer type SFCL with two triggering current levels

Citations

WEB OF SCIENCE

22
Citations

SCOPUS

22

초록

In this paper, the transformer type superconducting fault current limiter (SFCL) with two triggering current levels was suggested and its current limiting characteristics were analyzed. The structure of the suggested transformer type SFCL with two triggering current levels largely consists of two parts. One is the transformer with two magnetically coupled coils, which correspond to the primary winding and the secondary one connected with one high-T-C superconducting (HTSC) element. The other is third coil, or, another secondary winding with one HTSC element, which is wound on the same iron core together with two coils. This suggested transformer type SFCL can limit the fault current by generating its limiting impedance with two different amplitudes, which are dependent on the initial amplitude of the fault current in case of the fault occurrence. To confirm the usefulness of the proposed SFCL, the current limiting tests of the SFCL according to the fault angle, one of the effective fault conditions to affect the amplitude of the initial fault current, were carried out and its effective limiting operations were discussed. (C) 2012 Elsevier B.V. All rights reserved.

키워드

Transformer type superconducting fault current limiter (SFCL); Two triggering current levels; Fault current; Limiting impedance
제목
Analysis on current limiting characteristics of a transformer type SFCL with two triggering current levels
저자
Lim, Sung-Hun; Ko, Seckcheol; Han, Tae-Hee
DOI
10.1016/j.physc.2012.03.011
발행일
2013-01
유형
Article; Proceedings Paper
저널명
Physica C: Superconductivity and its Applications
권
484
페이지
253 ~ 257