Analysis of ignition time/current characteristics and energy when series arc-fault occurs at rated 220 V

  • Ko, W.-S.; 
  • Moon, W.-S.; 
  • Bang, S.-B.; 
  • Kim, J.-C.
Citations

SCOPUS

5

초록

Probability of ignition due to arc-fault and energy of the arc-fault for the case of applying serial arc-fault interruption time of 120 V defined in UL 1699 to the voltage of 220 V of domestic condition and also for the case of applying it to the HIV wire type are analyzed. It has been confirmed that when the arc-fault occurs under 5 A, 10 A, and 20 A. Probability of ignition for the three different current conditions is 0.74(74%), 0.48(48%), and 0.32(32%) respectively for respective interruption time within 1 sec, 0.4 sec, and 0.2 sec. We discover that when we apply the same arc interruption time for 120 V defined in UL 1699 to the domestic environment of 220 V. The probability of ignition increases from 1.5% for 120 V condition to as much as 74% for 220 V condition. Conclusively, if we apply the standard for the serial arc-fault interruption time defined in UL 1699 for 120 V to the domestic condition of 220 V, the fire prevention effect of electric fire due to arc-fault equal to that of UL standard of 120 V can not be achieved.

키워드

AFCI; Arc energy; Arc-fault; Ignition time/current; Series arc
제목
Analysis of ignition time/current characteristics and energy when series arc-fault occurs at rated 220 V
저자
Ko, W.-S.; Moon, W.-S.; Bang, S.-B.; Kim, J.-C.