Impact of distribution system quality on DG interconnection protection

초록

This paper has analyzed the impact of distribution power quality, especially unbalancing and triplen harmonic, on DG interconnection protection. We explored that the unbalanced single phase loads increase neutral current at DG interconnect transformer by analysis of measured data and simulation of PSCAD/EMTDC. An impact of triplen harmonic on DG interconnection transformers which are grounded wye (utility)-delta (DG) was also studied in same method. We confirmed that the power quality should be considered carefully for setting of ground overcurrent trip pick up level. ©2010 IEEE.

제목
Impact of distribution system quality on DG interconnection protection
저자
Cho, S.-M.; Shin, H.-S.; Kim, J.-C.
DOI
10.1109/PES.2010.5589431
발행일
2010
학회명
IEEE PES General Meeting, PES 2010
개최지
Minneapolis, MN
학회 개최일
2010-07-25 ~ 2010-07-29