단상 계통연계 인버터를 위한 개선된 고조파 보상법

An Improved Harmonic Compensation Method for a Single-Phase Grid Connected Inverter

초록

Grid-connected inverters should satisfy a certain level of total harmonic distortion (THD) to meet harmonics standards, such as IEEE 519 and P1547. The output quality of an inverter is typically degraded due to grid voltage harmonics, dead time effects, and the device’s turn-on/turn-off delay, which all contribute to increasing the THD value of the output. The use of a harmonic controller is essential to meet the required THD value for inverter output under a distorted grid condition. In this study, an improved feedforward harmonic compensation method is proposed to effectively eliminate low-order harmonics in the inverter current to the grid. In the proposed method, harmonic components are directly compensated through feedforward terms generated by the proportional resonant controller with the grid current in a stationary frame. The proposed method is simple to implement but powerful in eliminating harmonics from the output. The effectiveness of the proposed method is verified through simulation using PSIM software and experiments with a 5 kW single-phase grid-connected inverter.

키워드

SPGCI(Single Phase Grid Connected Inverter)Harmonic compensation methodTHD(Total Harmonic Distortion)Harmonic standard
제목
단상 계통연계 인버터를 위한 개선된 고조파 보상법
제목 (타언어)
An Improved Harmonic Compensation Method for a Single-Phase Grid Connected Inverter
저자
칸레이안최우진
DOI
10.6113/TKPE.2019.24.3.215
발행일
2019-06
저널명
전력전자학회 논문지
23
3
페이지
215 ~ 227