Study on current limiting characteristics of SFCL with two trigger current levels

초록

In this paper, the superconducting fault current limiter (SFCL) with two trigger current levels was suggested and its effectiveness through the analysis on the current limiting characteristics was described. The proposed SFCL, which consists of the triggering and the limiting components, can limit the fault current by generating the limiting impedance through two steps according to the amplitude of the initial fault current. In case that the fault happens, the lower initial fault current causes the only superconducting element of the triggering component to be quenched. On the other hand, the higher initial fault current makes both the superconducting elements comprising the triggering and the limiting components of the SFCL to be quenched, which contributes to the higher impedance of the SFCL. Therefore, the effective fault current limiting operation of the SFCL can be performed by generating the SFCL's impedance in proportion to the amplitude of the initial fault current. To confirm the current limiting operation of the proposed SFCL, the short-circuit tests of the SFCL according to the fault angle were carried out and its effective fault current limiting operations could be discussed. (C) 2010 Elsevier B.V. All rights reserved.

제목
Study on current limiting characteristics of SFCL with two trigger current levels
저자
Lim, S. H.
DOI
10.1016/j.physc.2010.05.177
발행일
2010-11-01
개최국가
네덜란드