Even Harmonic Analysis of Series Arc-fault Current Using BPF of GIC Application in Computer

GIC 적용 대역통과필터를 이용한 컴퓨터 부하의 직렬 아크고장 전류 우수고조파 분석
  • 고원식; 
  • 문원식; 
  • 방선배; 
  • 김재철
Citations

SCOPUS

0

초록

In this paper, the even harmonic current(2nd, 4th, 6th, 8th) of the arc fault current and normal current were measured in computer load and analyzed. The BPF with GIC was developed to detection of harmonic, the exact center frequency and a high degree of sharpness could be easily obtained. The total even harmonic distortion due to series arc fault in computer load was 31.2%, this value was increased 3.9 times better than the total even harmonic distortion of normal current. The results of analysis of arc fault current RMS variation rate and Peak variation rate per half-cycle,The RMS average variation rate are as follows ; the 2nd harmonic was 0.24, the 4th harmonic was 0.15, the 6th harmonic was 0.19, the 8th harmonic was 0.25, respectively. The Peak average variation rate are as follows ; the 2nd harmonic was 0.19, the 4th harmonic was 0.12, the 6th harmonic was 0.13, the 8th harmonic was 0.15, respectively. The results of this analysis utilize data to detect of series arc fault on wiring of computer load.

키워드

Arc-fault; Series arc; GIC; BPF; Even harmonic; Computer
제목
Even Harmonic Analysis of Series Arc-fault Current Using BPF of GIC Application in Computer
제목 (타언어)
GIC 적용 대역통과필터를 이용한 컴퓨터 부하의 직렬 아크고장 전류 우수고조파 분석
저자
고원식; 문원식; 방선배; 김재철
DOI
10.5370/KIEE.2012.61.10.1554
발행일
2012-10
유형
Article
저널명
전기학회논문지
권
61
호
10
페이지
1554 ~ 1560