Recently, the development of the electric power industry has led to an increase in the fault current when a fault occurs. It is important to reduce the fault current, since fault currents exceeding the capacity of protective devices can result in large blackouts. In order to reduce the fault current, there is a method to separate the bus line of main substation. However, this method has the disadvantage of complicating the power system. Another method is to install a superconducting fault current limiter (SFCL). The SFCL has the advantage that the fault current can be quickly limited within 1/4 cycle immediately after the fault occurrence without affecting the power system since its impedance is zero in a normal time. However, the application of SFCL affects the operation of the over-current relay (OCR) due to the reduced fault current such as trip time delay. The trip time delay of OCR was reported to be suppressed by using SFCL's voltage component in previous studies. In this paper, the impedance compensation method was suggested to exclude the effect of SFCL on OCR. To prevent OCR from the influence of SFCL, the component that can exclude the impedance of SFCL was considered to be added to the characteristic formula of OCR. In addition, the effect of correcting this characteristic equation was analyzed by constructing a power distribution system using PSCAD / EMTDC. IEEE

키워드

Analytical models; Circuit faults; Fault currents; Impedance; impedance compensation method; Mathematical model; Optical character recognition software; over-current relay (OCR); Power distribution; superconducting fault current limiter (SFCL); trip time delay; Electric industry; Electric power system protection; Fault current limiters; Time delay; Characteristic equation; Characteristic formula; Electric power industries; Impedance compensation; Overcurrent relays; Power distribution system; Protective devices; Superconducting faultcurrent limiters (SFCL); Superconducting fault current limiters
제목
Impedance Compensation Method of Protective Relay for SFCL's Application in a Power Distribution System
저자
Park, M.; Lim, S.
DOI
10.1109/TASC.2021.3059989
발행일
2021-08
유형
Article
저널명
IEEE Transactions on Applied Superconductivity
권
31
호
5