Study on Fault Current Limiting Characteristics of an SFCL Using Magnetic Coupling of Two Coils With Mechanical Switch Driven by Electromagnetic Repulsion Force

Citations

WEB OF SCIENCE

6
Citations

SCOPUS

11

초록

In this paper, the superconducting fault current limiter (SFCL) using magnetic coupling of two coils with mechanical switch, which the extra driving coil to drive it unlike the previous hybrid SFCL was not required, was suggested. The operational principle of the suggested SFCL using magnetic coupling of two coils with the mechanical switch is basically the same as one without mechanical switch, except that the mechanical switch is driven by the electromagnetic repulsion force generated by the magnetic flux between two coils comprising the SFCL. With the operation of the mechanical switch, the fault current flowing through the SFCL using magnetic coupling of two coils can be commutated from the magnetically coupled two coils into the coil operated as the current limiting reactor (CLR) immediately after the fault occurs, which is contributed to the fault current limiting operation of this SFCL. To verify the operation of the suggested SFCL, the mechanical switch with electromagnetic contact comprised of the fixed and the moving parts, which were located just above open iron core wound by two parallel connected coils, was designed and fabricated. With the fabricated mechanical switch, the short-circuit tests of the SFCL with the suggested mechanical switch were carried out. Through the analysis on the results of the short-circuit tests, the current limiting characteristics of the suggested SFCL with the mechanical switch could be confirmed to be improved effectively with the reduction of the power burden of the high-T-C superconducting (HTSC) element comprising the SFCL.

키워드

Electromagnetic repulsion force; magnetic coupling; mechanical switch; short-circuit test; Superconducting Fault Current Limiter (SFCL); LOCK TYPE SFCL; WINDING DIRECTION; PERFORMANCE
제목
Study on Fault Current Limiting Characteristics of an SFCL Using Magnetic Coupling of Two Coils With Mechanical Switch Driven by Electromagnetic Repulsion Force
저자
Lim, Sung-Hun; Ahn, Hyeong-Joon; Park, Changkun
DOI
10.1109/TASC.2013.2284853
발행일
2014-06
유형
Article
저널명
IEEE Transactions on Applied Superconductivity
권
24
호
3