식물성 절연유 변압기의 냉각특성 변화에 따른 최고점온도 특성 해석

Characteristic Analysis of Hot Spot Temperature according to Cooling Performance Variation of Natural Ester Transformer

초록

Natural ester has a higher biodegradability, flash and fire points, and a greater permittivity compared to conventional mineral oils. However, natural ester also has a higher pour point, viscosity, and water content. These characteristics hamper circulation and the electrical properties of oil-filled transformer. Thus, this paper applied electromagnetic-thermal-flow coupled analysis method to predict temperature distribution inside 154kV single phase power transformer using natural ester. It modeled in the actual appearance for the tank and winding of the power transformer to improve the accuracy of analysis and applied heat flow analysis that considered hydromechanics and heat transfer at the same time. It calculated the power loss, the main cause of temperature rise, from winding and core with electromagnetic analysis then used for the heat source for the heat flow analysis. It then compared the reasonability of result of measurement analysis based on the result acquired from temperature rise test using FBG sensor on the power transformer.

키워드

CFD analysisCooling performanceNatural esterPower transformerTemperature rise test
제목
식물성 절연유 변압기의 냉각특성 변화에 따른 최고점온도 특성 해석
제목 (타언어)
Characteristic Analysis of Hot Spot Temperature according to Cooling Performance Variation of Natural Ester Transformer
저자
김지호이향범
발행일
2015-12
저널명
전기학회 논문지 P권
64
4
페이지
236 ~ 240