초록
The on-line partial discharge (PD) in stator windings of air-cooled gas turbine (GT) generator (119.2MVA, 13.8kV) is measured and analyzed in this paper. This generator was designed by global vacuum pressure impregnation (VPI). The generator failed two times at top bar (16T) of phase B in the stator slot. Six epoxy-mica capacitors were installed in three phases of GT generator. On-line PD test was performed on GT generator using turbine generator analyzer (TGA). TGA showed that the normalized quantity number (NQN) and the PD magnitude(Qm) were high in phase B. Internal discharges were generated in phases A, B and C. The trend analysis of NQN and Qm value are obtained in order to monitor the insulation condition in GT generator stator windings. Phases A and C were in good condition. But phase B had deteriorated significantly.
키워드
- 제목
- 공랭식 가스터빈 발전기의 운전중 부분방전 분석
- 저자
- 이은춘; 공태식; 김재철; 김희동
- 발행일
- 2014
- 저널명
- 조명.전기설비학회논문지
- 권
- 28
- 호
- 7
- 페이지
- 41 ~ 47
- 출판사
- 한국조명.전기설비학회
- 발행국가
- 대한민국
- 분량
- 7 페이지
- ISSN
- P 1229-4691